LOAD FACTOR


What is load factor used for in power system?
Load factor in electrical context is defined as the ratio between the Average Load of the electrical system to the Maximum Demand that it attained. This is factor is used to determine the level of difference between the average load to the peak load. Like the Demand Factor, Load factor is also expressed in percentage form.


where:




Since losses increase with the square of the load current (I)squared and since the cost of losses is highest at the peak load periods, the relationship between the peak load on a system component and its average loading is important in any study of losses on that component that is why load factor is a key factor used to describe the relationship between peak and average loads and is calculated in the above shown formula. (TVPPA, nov.1994)

The ideal value for Load factor is 100%, this means that the consumed load by the system is just enough for the capacity to cater. Having a low Load factor means the system capacity is not maximized for the reason that the difference between the average load and the peak demand is high. This translates to the utility putting up capacity that is most of the time idle.

Sample Computation:

A certain mall which is a contestable customer was read with an average monthly load of 277.8kW while the maximum registered meter demand reached 380 kW. So, what is their load factor?

LF = (Average Load) / (Maximum Demand) = 277.8kW/380kW = 73.1%

Comments

Popular posts from this blog

PARTS OF A POWER TRANSFORMER

What are the name of the basic parts of a Power Transformer? We can not deny the fact that only a handful of electrical engineering students are presently familiar with power transformers especially on what it looks like. Unlike a transformer we found in our homes, a power transformer’s appearance and construction is somewhat more complicated. It is not just a simple winding with a primary and secondary terminal although basically any transformer has one. The function that a power transformer plays in an electrical system is very important that an electric utility can not afford to loss it during its operation. Our discussion here will focus more on the basic parts and functions of a power transformer that are usually tangible whenever you go to a substation . Although not all power transformers are identical, nonetheless they all have the following listed parts in which the way of construction may differ.

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS How is electric motor frame size being specified? Motor frame dimensions have been standardized with a uniform frame size numbering system. This system was developed by NEMA and specific frame sizes have been assigned to standard motor ratings based on enclosure, horsepower and speed. The current standardized frames for integral horsepower induction motors ranges from 143T to 445T. These standards cover most motors in the range of one through two hundred horsepower. Typical example of where you can locate the frame is shown in Fig 1.2.D – Frame No. The numbers used to designate frame sizes have specific meanings based on the physical size of the motor. Some digits are related to the motor shaft height and the remaining digit or digits relate to the length of the motor. The rerate, or frame size reduction programs were brought about by advancements in motor technology relating mainly to higher temperature ratings of insulating mate

ELECTRIC MOTOR NAMEPLATE SPECIFICATIONS

How do we interpret an electric motor nameplate? Motor standards are established on a country by country basis.Fortunately though, the standards can be grouped into two major categories: NEMA and IEC (and its derivatives). In North America, the National Electric Manufacturers Association (NEMA) sets motor standards, including what should go on the nameplate (NEMA Standard MG 1-10.40 "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors").