ANSI C57.12.20-1997: STANDARD FOR OVERHEAD TYPE DISTRIBUTION TRANSFORMERS, 500KVA AND SMALLER: HIGH VOLTAGE, 34500 VOLTS AND BELOW: LOW VOLTAGE, 7970/13800Y VOLTAS AND BELOW

ANSI C57.12.20-1997: STANDARD FOR OVERHEAD TYPE DISTRIBUTION TRANSFORMERS, 500KVA AND SMALLER: HIGH VOLTAGE, 34500 VOLTS AND BELOW: LOW VOLTAGE, 7970/13800Y VOLTAS AND BELOWANSI standard C57.12.20-1997 on overhead type distribution transformer

Scope: This standard is intended for use as a basis for determining the performance, interchangeability, and safety of the equipment covered, and to assist in the proper selection of such equipment.

This standard covers certain electrical, dimensional, and mechanical characteristics and takes into consideration certain safety features of single- and three-phase, 60-Hz, mineral-oil-immersed, self-cooled, overhead-type distribution transformers 500 kVA and smaller, with high voltages 34500 volts and below and low voltages 7970/13800Y volts and below. Such transformers may include one or more of the following features:

1) High-voltage, overcurrent protection
2) High-voltage, overvoltage protection
3) Low-voltage, overcurrent protection
4) Low-voltage, overvoltage protection

This standard is intended for use in conjunction with the following American National Standards. All characteristics, definitions, terminology, voltage designations, and tests, except as specified herein, shall be in accordance with these referenced American National Standards. When the following referenced standards are superseded by a revision approved by the American National Standards Institute, Inc., the latest revision shall apply.

Ratings: Kilovolt-ampere ratings are continuous and are based on not exceeding either a 65°C average winding temperature rise or an 80°C hot-spot temperature rise. The temperature rise of the insulating oil shall not exceed 65°C when measured near the top of the tank. Kilovolt-ampere ratings for single-phase and three-phase transformers shall be as shown in Table 1. These ratings are based on the usual temperature and altitude service conditions specified in ANSI/IEEE C57.12.00 .

Voltage ratings for single-phase and three-phase transformers shall be in accordance with Tables 2, 3, and 4. No taps are to be provided unless otherwise specified in accordance with 3.2.2

Comments

Popular posts from this blog

PARTS OF A POWER TRANSFORMER

What are the name of the basic parts of a Power Transformer? We can not deny the fact that only a handful of electrical engineering students are presently familiar with power transformers especially on what it looks like. Unlike a transformer we found in our homes, a power transformer’s appearance and construction is somewhat more complicated. It is not just a simple winding with a primary and secondary terminal although basically any transformer has one. The function that a power transformer plays in an electrical system is very important that an electric utility can not afford to loss it during its operation. Our discussion here will focus more on the basic parts and functions of a power transformer that are usually tangible whenever you go to a substation . Although not all power transformers are identical, nonetheless they all have the following listed parts in which the way of construction may differ.

ELECTRIC MOTOR NAMEPLATE SPECIFICATIONS

How do we interpret an electric motor nameplate? Motor standards are established on a country by country basis.Fortunately though, the standards can be grouped into two major categories: NEMA and IEC (and its derivatives). In North America, the National Electric Manufacturers Association (NEMA) sets motor standards, including what should go on the nameplate (NEMA Standard MG 1-10.40 "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors").

DISADVANTAGES OF Y-Y CONNECTION IN THREE PHASE SYSTEM

What are the disadvantages in using y-y connection? The Y-Y transformer connection was poorly understood in the early days of power engineering and it received a very bad reputation when it was first used; in fact, this connection was avoided for a long time until its limitations were overcome by good engineering practice. Some of the inherent disadvantages of the Y-Y connection are discussed below: