SUBSTATION CAPACITORS IN REDUCING POWER LOSSES


What is the difference between substation capacitor and line capacitors?

If capacitors are installed primarily to reduce or eliminate bulk power charges for kVAR or for other reasons associated with wholesale purchased power such as contractual requirements, they can be installed in substations to supplement distribution line installations. Installed equipment cost for substation capacitors may be less than that for the same amount of line kVAR because the substation units can package many kVAR in a single installation and can be switched with a single three-phase switching device and control unit. However, the distributor does not get the benefit of reduced distribution line losses by installing capacitors at substations, so such installations should be made only after the maximum practical amount of line capacitors has been installed.

                      “Substation capacitors: To supplement, not replace distribution line capacitors.”

Problems can develop from the switching of substation capacitors if engineering and operations planning is inadequate. One possible problem is the production of a noticeable voltage spike when a large block of substation capacitors is switched at one time.

Another possible problem with substation capacitors is the disruption of capacitor switching control settings when one transformer is taken out of service in a two-transformer substation. The change in source impedance can cause a voltage-controlled capacitor switch with a narrow band width to switch on and off rapidly. Capacitor switching equipment has been known to fail violently under this condition. Avoidance of capacitor switching solely on voltage will eliminate this problem. If voltage controlled capacitors are used in two-transformer substations, the switching control should be placed on manual during maintenance work when one transformer is taken out of service.

                                                 Technical Requirements Of Capacitor Bank
                                                Data To Be Submitted With Request for Quote

1. Bank voltage ________kV

2. Frequency _________HZ

3. Bank Capacitance: ________Initial ________Future

4. Bank KV-BIL: ________

 5. Connection _____Grounded _____Ungrounded Wye

6. Capacitor mounting _____Horizontal _____Vertical

7. Fusing _____Expulsion _____Current limiting

8. Bushing creepage: _____10" _____18" _____22" _____26"

9. Elevating structure: _____Ht. in inches

10. Temp Range: _____Min _____Max

11. Unbalanced scheme to be supplied with tender: ___Yes ___No

12. Describe any unusual service conditions.


Comments

Popular posts from this blog

PARTS OF A POWER TRANSFORMER

What are the name of the basic parts of a Power Transformer? We can not deny the fact that only a handful of electrical engineering students are presently familiar with power transformers especially on what it looks like. Unlike a transformer we found in our homes, a power transformer’s appearance and construction is somewhat more complicated. It is not just a simple winding with a primary and secondary terminal although basically any transformer has one. The function that a power transformer plays in an electrical system is very important that an electric utility can not afford to loss it during its operation. Our discussion here will focus more on the basic parts and functions of a power transformer that are usually tangible whenever you go to a substation . Although not all power transformers are identical, nonetheless they all have the following listed parts in which the way of construction may differ.

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS How is electric motor frame size being specified? Motor frame dimensions have been standardized with a uniform frame size numbering system. This system was developed by NEMA and specific frame sizes have been assigned to standard motor ratings based on enclosure, horsepower and speed. The current standardized frames for integral horsepower induction motors ranges from 143T to 445T. These standards cover most motors in the range of one through two hundred horsepower. Typical example of where you can locate the frame is shown in Fig 1.2.D – Frame No. The numbers used to designate frame sizes have specific meanings based on the physical size of the motor. Some digits are related to the motor shaft height and the remaining digit or digits relate to the length of the motor. The rerate, or frame size reduction programs were brought about by advancements in motor technology relating mainly to higher temperature ratings of insulating mate

ELECTRIC MOTOR NAMEPLATE SPECIFICATIONS

How do we interpret an electric motor nameplate? Motor standards are established on a country by country basis.Fortunately though, the standards can be grouped into two major categories: NEMA and IEC (and its derivatives). In North America, the National Electric Manufacturers Association (NEMA) sets motor standards, including what should go on the nameplate (NEMA Standard MG 1-10.40 "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors").