Skip to main content

TYPES OF CAPACITOR INSTALLATIONS


TYPES OF CAPACITOR INSTALLATIONS
What are the types of Capacitor Installation known?

Capacitors are relatively easy to install and are among the most trouble-free electrical devices. Line capacitor installations are protected with conventional cut-out fused switches, and capacitor failure is rare if the appropriate fuse element is used. (Fuse rating should be closely coordinated with capacitor size.) There are several types of capacitors (see figure below).


capacitor

Following Load Reactive Power

The most difficult aspect of capacitor application is the maintenance of proper balance between total kVAR of capacitors connected at any particular time and load kVAR present at that time. Like load kW, load kVAR changes over time, so some provision must be made to vary the total connected capacitive kVAR to roughly follow the load kVAR. Installing capacitors based on the peak load kVAR and leaving all these capacitors connected at off-peak times is strictly inadvisable, since excessive capacitive kVAR would exist on the system during light load periods. This would result in an overall leading power factor for the feeder involved, and a leading power factor increases line amperes in the same manner that a lagging power factor does. A leading power factor can cause other problems also, such as excessive line voltage and harmonics.
An example of the consequences of failing to remove capacitors that are too large for the load kVAR occurred on part of the system of an actual rural electric cooperative. A 600-kVAR capacitor was installed near the location of an industrial consumer, and the capacitor was not removed after the consumer went out of business. The losses on the small whole sale metering point increased from 3.5% to 23%. The cause was not immediately identified because power-factor metering at the supply point indicated that the power factor was 85%, but it did not identify whether the power factor was leading or lagging. In this case, the power factor was leading because of the excessive capacitive kVAR on the feeder. In addition to the above reasons, distributors should avoid leading kVAR because the Reactive Demand Charges clause of the TVA WS rate schedule contains charge for leading power factor at delivery points. The charge is 33 cents per leading kVAR at the time of minimum load for each month. This seemingly modest charge can accumulate into a significant amount in dollars if hundreds of leading kVAR are present month after month.

Switched and Fixed Capacitors

The total kVAR of connected capacitors is controlled by installing automatic switching on some of the capacitors. The units equipped with switches, called switched capacitors are removed from the line during light load periods so the remaining connected capacitive kVAR will closely agree with the load kVAR. Since a base amount of load kVAR remains even during minimum load, some capacitors can be connected permanently to the line. Capacitors that remain connected to the line at all times are called fixed capacitors.

Comments

Popular posts from this blog

PARTS OF A POWER TRANSFORMER

What are the name of the basic parts of a Power Transformer? We can not deny the fact that only a handful of electrical engineering students are presently familiar with power transformers especially on what it looks like. Unlike a transformer we found in our homes, a power transformer’s appearance and construction is somewhat more complicated. It is not just a simple winding with a primary and secondary terminal although basically any transformer has one. The function that a power transformer plays in an electrical system is very important that an electric utility can not afford to loss it during its operation. Our discussion here will focus more on the basic parts and functions of a power transformer that are usually tangible whenever you go to a substation . Although not all power transformers are identical, nonetheless they all have the following listed parts in which the way of construction may differ.

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS How is electric motor frame size being specified? Motor frame dimensions have been standardized with a uniform frame size numbering system. This system was developed by NEMA and specific frame sizes have been assigned to standard motor ratings based on enclosure, horsepower and speed. The current standardized frames for integral horsepower induction motors ranges from 143T to 445T. These standards cover most motors in the range of one through two hundred horsepower. Typical example of where you can locate the frame is shown in Fig 1.2.D – Frame No. The numbers used to designate frame sizes have specific meanings based on the physical size of the motor. Some digits are related to the motor shaft height and the remaining digit or digits relate to the length of the motor. The rerate, or frame size reduction programs were brought about by advancements in motor technology relating mainly to higher temperature ratings of insulating mate

ELECTRIC MOTOR NAMEPLATE SPECIFICATIONS

How do we interpret an electric motor nameplate? Motor standards are established on a country by country basis.Fortunately though, the standards can be grouped into two major categories: NEMA and IEC (and its derivatives). In North America, the National Electric Manufacturers Association (NEMA) sets motor standards, including what should go on the nameplate (NEMA Standard MG 1-10.40 "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors").