69KV CURRENT TRANSFORMER SAMPLE TECHNICAL SPECIFICATION

69KV CURRENT TRANSFORMER SAMPLE TECHNICAL SPECIFICATION
Sample specification of a 69kv Current Transformer.

Description:

For Oil-Filled Type:
The unit shall be hermetically sealed and of the minimum oil-filed type and compact design. All sealing shall be located below the oil level. The expansion room shall be of a gas cushion type filled with nitrogen. Oil level should be of the reflection type and without moving parts. Primary terminals shall be suitable for connection of copper or aluminum connectors. The external ferrous parts shall be of hair pin type insulation consisting of oil-impregnated paper and capacitor layers for voltage grading. It should be preferably provided with a capacitance voltage tap throughout thru an insulated, factory grounded, bushing for checking the condition of its primary insulation. It should have a high seismic withstand capability of 0.5G. The unit must be able to be tilted to 60 deg. C.

For Gas Type:
The primary and secondary winding of the SF6 Gas Insulated shall be housed in a non-corrosive cylinder hermetically sealed type, preventing any contact of the SF6 with the atmosphere by means of separate flexible diaphragm.

The instrument transformer shall have the following built-in devices:
• A Pressure Relief Device that is set to trigger at the designed over-pressure value.
• An SF6 Gas Pressure Indicator with pressure graduations showing the Normal and High/Low danger levels of SF6 Gas Pressure.
• Pressure switches with two (2) sets of NO/NC contacts for  connection with the Substation Alarm/Protection Circuits.
 - One (1) set of contacts calibrated to trigger at Low Pressure Alarm Level
- One (1) set of contacts calibrated to trigger at Low Pressure Danger Level

Type    Outdoor Type, Minimum Oil-filled or Gas Insulated
Cooling    Oil-immersed/ Gas insulated, self-cooled
Model    Extended Range
Construction   Single phase, wound type, free standing
Accuracy Class   0.3 or better thru B-0.1 up to B-1 for both cores and at all taps
Compliance to Standard  ANSI/IEEE C57.13 or applicable IEC
Rating Factor   1.5 at 30oC
Accuracy Range   1% up to 150 % 
BIL    350KV, 60Hz

Minimum Creepage Distance 1380 mm
Number of Core   Two (2)
CTR (Double Ratio) (To be computed based on the actual load)
Rated Secondary Current 5 A

Short Time Rating Current (per IEC)
1. Thermal Ith, KA  22
2. Dynamic, Idyn, KA 55

Mounting    Pedestal
Rated Frequency, Hz  60
Nominal System Voltage, KV 69
Maximum Continuous Voltage, KV 72.5

Post Insulator Characteristics
1. Voltage Class, KV  72.5
2. Color     Chocolate brown (preferred)
3. Creepage Length, mm  1380
Weight     240 kgs. (maximum)

Accessories:
• 1-set Primary Connectors, clamp type terminal of nickel-plated brass for horizontal connection of round aluminum or copper conductors.
• Secondary Connectors, 1 set- M10 split studs with 3.2 mm slot suitable for conductors of 8 mm2 across section with nuts for connecting cable lugs
• Grounding Connectors split studs, 1 set-Earthing clamp for a round conductors or line of 5-16 mm diameter.
• There should be provisions for the installation of security seals on the secondary terminal box. (e.g. seal holder, etc.).
Requirements/Conditions:
• Factory test results and Type Approval Test Report of the CT from an independent regulating body or international organizations.
• Field reference, catalogues, drawings, hardware and instruction user’s manual.
• Declaration and proof that the manufacturer should have been in the business of manufacturing the equipment of not less than ten (10) years.

Comments

  1. Nice post thanx for sharing with us

    AR Engineering is leading manufacturer of Varnishing Machines manufacturer in pune ,Maharashtra, India. Transformation oil filtration machine in india, oil purification plants,Transformer oil filtration machines in pune.


    Varnishing Machines suppliers in pune

    Trickle Impregnation Technique manufacturer in pune

    Transformer Oil Filtration Plants manufacturer in pune

    industrial oil filtration plant

    Vacuum Impregnation Plants

    Index Type Trickle Impregnating Machine manufacturer in pune

    Batch Type Trickle Impregnating Machine manufacturer in pune

    ReplyDelete
  2. Nice articles and your information valuable and good articles thank for the sharing information Transformer Oil Filtration Plant

    ReplyDelete

Post a Comment

Popular posts from this blog

PARTS OF A POWER TRANSFORMER

What are the name of the basic parts of a Power Transformer? We can not deny the fact that only a handful of electrical engineering students are presently familiar with power transformers especially on what it looks like. Unlike a transformer we found in our homes, a power transformer’s appearance and construction is somewhat more complicated. It is not just a simple winding with a primary and secondary terminal although basically any transformer has one. The function that a power transformer plays in an electrical system is very important that an electric utility can not afford to loss it during its operation. Our discussion here will focus more on the basic parts and functions of a power transformer that are usually tangible whenever you go to a substation . Although not all power transformers are identical, nonetheless they all have the following listed parts in which the way of construction may differ.

ELECTRIC MOTOR NAMEPLATE SPECIFICATIONS

How do we interpret an electric motor nameplate? Motor standards are established on a country by country basis.Fortunately though, the standards can be grouped into two major categories: NEMA and IEC (and its derivatives). In North America, the National Electric Manufacturers Association (NEMA) sets motor standards, including what should go on the nameplate (NEMA Standard MG 1-10.40 "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors").

DISADVANTAGES OF Y-Y CONNECTION IN THREE PHASE SYSTEM

What are the disadvantages in using y-y connection? The Y-Y transformer connection was poorly understood in the early days of power engineering and it received a very bad reputation when it was first used; in fact, this connection was avoided for a long time until its limitations were overcome by good engineering practice. Some of the inherent disadvantages of the Y-Y connection are discussed below: