69KV VOLTAGE TRANSFORMER SAMPLE TECHNICAL SPECIFICATION

69KV VOLTAGE TRANSFORMER SAMPLE TECHNICAL SPECIFICATION
Sample specification of a 69kv Voltage Transformer.

Description:
The unit should be magnetic type and for connection between phase and earth in networks with isolated or earthed neutral.

• Designed with low flux density in the core and can therefore be operated at 190% rated voltage for more than 8 hours
• Fitted with a secondary measuring winding and a tertiary earth-fault winding
• Hermetically sealed, which means no need for regular maintenance procedures
• Primary terminals shall be suitable for connection of copper or aluminum connectors.
• All external parts are hot-dip galvanized
• High seismic withstand capability (0.5G)

For Oil-Filled Type:
The unit shall be hermetically sealed and of the minimum oil-filed type and compact design. All sealing shall be located below the oil level. The expansion room shall be of a gas cushion type filled with nitrogen. Oil level should be of the reflection type and without moving parts. The external ferrous parts shall be of hair pin type insulation consisting of oil-impregnated paper and capacitor layers for voltage grading. The unit must be able to be tilted to 60 deg. C.

For Gas Type:
The primary and secondary winding of the SF6 Gas Insulated shall be housed in a non-corrosive cylinder hermetically sealed type, preventing any contact of the SF6 with the atmosphere by means of separate flexible diaphragm.

The instrument transformer shall have the following built-in devices:
• A Pressure Relief Device that is set to trigger at the designed over-pressure value.
• An SF6 Gas Pressure Indicator with pressure graduations showing the Normal and High/Low danger levels of SF6 Gas Pressure.
• Pressure switches with two (2) sets of NO/NC contacts for connection with the Substation Alarm/Protection Circuits.
 - One (1) set of contacts calibrated to trigger at Low Pressure Alarm Level
- One (1) set of contacts calibrated to trigger at Low Pressure Danger Level

Type Outdoor Type, Minimum Oil-filled or Gas Insulated
Cooling Oil-immersed/ Gas insulated, self-cooled
Construction Single phase, Inductive type, Single bushing
Termination Line-to-ground
Accuracy Class 0.3 or better through burden W up to Y for both cores & taps
Compliance to Standard   ANSI/IEEE C57.13 or applicable IEC
Nominal System Voltage, KV     69
Maximum Continuous System Voltage, KV 72.5
BIL, KV      350
Rated Frequency, Hz    60

Rated withstand & Test Voltage, KV
• Low frequency withstand, KV RMS 140
• Impulse lightning withstand, KV crest  325

Minimum creepage distance   1725 mm
No. of core     Two (2)
Single Ratio (L-G)    40250V : 115V
PTR      350 :1
Available secondary voltage   115V
Mounting      Pedestal
Post Insulator Characteristics
• Voltage class, KV   72.5
• Color      Chocolate brown (preferred)
• Creepage Length, mm   1725
Weight      320 kgs. (maximum)

Accessories:
• 1-set Primary Connectors, clamp type terminal of nickel-plated brass for horizontal connection of round aluminum or copper conductors.
• Secondary Connectors, 1 set- M10 split studs with 3.2 mm slot suitable for conductors of 8 mm2 across section with nuts for connecting cable lugs
• Grounding Connectors split studs, 1 set-Earthing clamp for a round conductors or line of 5-16 mm diameter.
• There should be provisions for the installation of security seals on the secondary terminal box. (e.g. seal holder, etc.)

REQUIREMENTS/CONDITIONS
• Factory test results and Type Approval Test Report of the PT from an independent regulating body or international organizations.
• Field reference, catalogues, drawings, hardware and instruction user’s manual.
• Declaration and proof that the manufacturer should have been in the business of manufacturing the equipment of not less than ten (10) years.

Comments

Popular posts from this blog

PARTS OF A POWER TRANSFORMER

What are the name of the basic parts of a Power Transformer? We can not deny the fact that only a handful of electrical engineering students are presently familiar with power transformers especially on what it looks like. Unlike a transformer we found in our homes, a power transformer’s appearance and construction is somewhat more complicated. It is not just a simple winding with a primary and secondary terminal although basically any transformer has one. The function that a power transformer plays in an electrical system is very important that an electric utility can not afford to loss it during its operation. Our discussion here will focus more on the basic parts and functions of a power transformer that are usually tangible whenever you go to a substation . Although not all power transformers are identical, nonetheless they all have the following listed parts in which the way of construction may differ.

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS How is electric motor frame size being specified? Motor frame dimensions have been standardized with a uniform frame size numbering system. This system was developed by NEMA and specific frame sizes have been assigned to standard motor ratings based on enclosure, horsepower and speed. The current standardized frames for integral horsepower induction motors ranges from 143T to 445T. These standards cover most motors in the range of one through two hundred horsepower. Typical example of where you can locate the frame is shown in Fig 1.2.D – Frame No. The numbers used to designate frame sizes have specific meanings based on the physical size of the motor. Some digits are related to the motor shaft height and the remaining digit or digits relate to the length of the motor. The rerate, or frame size reduction programs were brought about by advancements in motor technology relating mainly to higher temperature ratings of insulating mate

ELECTRIC MOTOR NAMEPLATE SPECIFICATIONS

How do we interpret an electric motor nameplate? Motor standards are established on a country by country basis.Fortunately though, the standards can be grouped into two major categories: NEMA and IEC (and its derivatives). In North America, the National Electric Manufacturers Association (NEMA) sets motor standards, including what should go on the nameplate (NEMA Standard MG 1-10.40 "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors").