Skip to main content

INSTRUMENT TRANSFORMERS: LOSSES IN THE POWER SYSTEM’S CONTRIBUTION

How Instrument transformer contributes to system losses?

Like any other transformer in general, Instrument transformers are intended to convert current or voltage from the high level in the transmission and distribution systems to the low levels that can be used by low voltage metering devices. Three primary applications for which instrument transformers are usually known: metering (for energy billing and revenue purposes); protection control (for system protection and protective relaying function); and load survey (for economic management of industrial loads).

The type of instrument transformer to be use can vary significantly depending on the necessities for those applications, the instrument transformer design and construction can be quite different. In general, the metering instrument transformers need high accuracy in the range of normal operating voltage and current. Protection instrument transformers need linearity in a wide range of voltages and currents.

During system fault, overvoltage transients, or any other disturbances, the output of the instrument transformer is used by a protective relay to initiate an suitable action (close or open a breaker, reconfigure the system, etc.) to alleviate the disturbance and protect the rest of the power system.

The most common and economic way to detect a disturbance is by using instrument transformers. Typical output levels of instrument transformers are 1-5 amperes and 115-120 volts for current transformers and voltage transformers, respectively. There are several classes of accuracy for instrument transformers defined by the international standards like IEEE, CSA, IEC, and ANSI.

Burdens
The errors in ratio and phase angle depend on the impedance connected to the secondary of the transformer. This impedance is commonly referred to as “burden”. The calculations required for determining the performance of a transformer when different burdens are applied are beyond the scope of this discussion. Therefore, the standard burdens as outlined in IEEE C57.13 are used to represent typical service conditions. Each transformer is rated according to its performance at these standard burdens.

Current Transformer Burden
Many current transformers supply only a limited number of watt-hour meter elements with a limited number of runs. For metering and relaying applications, IEEE C57.13 has established the standard burdens as given in Figure 9.

current transformer burden

Voltage Transformer Burden
The standard burdens to be used for testing and comparing voltage transformers are rated at 120 volts and at 69.3 volts. IEEE C57.13 specifies that the 120 volt-rated burden will be used for any transformer with the secondary voltage in the range of 115 to 120 volts, while the 69.3 volt burden will be used for any transformer with the secondary voltage in the range of 65 to 72 volts. This means that the actual volt amperes in the burden in a given test may be different than the nominal value of the burden in volt amperes. For instance, if the standard burden is 25 volt amperes, the actual burden when it is used for testing a transformer with 115 volt secondary is (115/120)2 or .918 times the nominal value of 25.

The burdens rated 69.3 volts have impedance only one-third of that of burdens rated 120 volts and they should not be used in testing or rating transformers rated at 115 to 120 volts. Transformers rated at 115 or 120 volts should be treated as 115 or 120 volt transformers, and if they are actually used at reduced voltage, the performance will not be different if the 120 volt burden is used as a basis for performance. This is because the performance of a transformer down to voltages of about 5% of its rating is not significantly different from the performance at 100% voltage. Refer to Figure 10 for standard burdens for voltage transformers as outlined in IEEE C57.13.


voltage transformer burden

A number of considerations are involved in selecting proper instrument transformers. Many of the transformer types have similar characteristics, but each type has its own unique combination of features that best meet the application for which it is designed.

Comments

Popular posts from this blog

PARTS OF A POWER TRANSFORMER

What are the name of the basic parts of a Power Transformer? We can not deny the fact that only a handful of electrical engineering students are presently familiar with power transformers especially on what it looks like. Unlike a transformer we found in our homes, a power transformer’s appearance and construction is somewhat more complicated. It is not just a simple winding with a primary and secondary terminal although basically any transformer has one. The function that a power transformer plays in an electrical system is very important that an electric utility can not afford to loss it during its operation. Our discussion here will focus more on the basic parts and functions of a power transformer that are usually tangible whenever you go to a substation . Although not all power transformers are identical, nonetheless they all have the following listed parts in which the way of construction may differ.

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS

ELECTRIC MOTOR FRAME SIZE STANDARD SPECIFICATIONS How is electric motor frame size being specified? Motor frame dimensions have been standardized with a uniform frame size numbering system. This system was developed by NEMA and specific frame sizes have been assigned to standard motor ratings based on enclosure, horsepower and speed. The current standardized frames for integral horsepower induction motors ranges from 143T to 445T. These standards cover most motors in the range of one through two hundred horsepower. Typical example of where you can locate the frame is shown in Fig 1.2.D – Frame No. The numbers used to designate frame sizes have specific meanings based on the physical size of the motor. Some digits are related to the motor shaft height and the remaining digit or digits relate to the length of the motor. The rerate, or frame size reduction programs were brought about by advancements in motor technology relating mainly to higher temperature ratings of insulating mate

ELECTRIC MOTOR NAMEPLATE SPECIFICATIONS

How do we interpret an electric motor nameplate? Motor standards are established on a country by country basis.Fortunately though, the standards can be grouped into two major categories: NEMA and IEC (and its derivatives). In North America, the National Electric Manufacturers Association (NEMA) sets motor standards, including what should go on the nameplate (NEMA Standard MG 1-10.40 "Nameplate Marking for Medium Single-Phase and Polyphase Induction Motors").