Principles in using single-phase transformers to create a three-phase banks.
There can be advantages to using single-phase transformers to make a three- phase bank instead of building a three-phase unit. For instance, it may be impossible or impractical to fabricate or ship a three-phase transformer with an extremely large MVA capacity.
A bank of three single-phase transformers may then be the solution, although the total size, weight, and cost of three single-phase units will probably exceed the size, weight, and cost of one three- phase unit. An additional advantage of the bank arrangement is that a failure of one single-phase unit will usually be less costly to repair than a failure of a larger three-phase unit.
Furthermore, one spare single-phase transformer is usually all that is required to assure sufficient reliability for the entire bank. With a threephase transformer, an additional spare three-phase transformer would be required, so the total cost of the installation plus a spare transformer is twice the cost of the installation alone.
The total cost of a bank of singlephase transformers plus a spare is only 133% the cost of the bank alone. Therefore, the total cost of a bank of single-phase transformers plus a spare is probably less than the cost of a three-phase transformer plus a spare.
Either Y or Δ connections are possible with single-phase transformers connected in banks. It is extremely important that the single-phase transformers are carefully matched when they are banked together, especially when the Δ connection is used.
Using mismatched transformers in the Δ connection will result in excessive circulating currents that will severely derate the bank or cause overheating. One interesting configuration for a three-phase bank is the open Y-Δ connection used extensively in rural distribution systems.
The open Y-Δ connection uses two single-phase transformers, as shown in Figure 9.16. An open Y-Δ connection requires only two phases plus the neutral on the primary side of the bank in order to develop a three-phase voltage at the secondary.
This is an obvious cost saving (in addition to the avoided cost of a third transformer) when the installation is far away from a three-phase primary circuit. If one of the transformers is center-tapped as shown in Figure 9.16, then the bank provides a single-phase lighting leg in addition to a three-phase power circuit.
Nice. Thanks for the great information. NEMR is known as one of the best 63kva Distribution Transformer. NEMR Industries provides reliable and efficient 63kva distribution transformer for smooth supply to varied uses. These transformers come with advanced features to assure stable voltage, minimize loss, and have no trouble even under tough conditions.